The digital detector designed to reduce cabling costs.

The OLCT 10N detector has been specially designed to detect the most commonly found gases in the commercial or light industry sector.

Intended for use via digital connection with the MX 43 control panel, the OLCT 10N provides a fast and accurate response. You can have up to 16 detectors on the same digital line or distribute 32 detectors across the 8 lines of an MX43. All the sensor and relay information is processed by the control panel in under one second.

With an ultra-bright LED and a magnet, calibration of the detector is automatic and does not require the housing to be opened.
The calibration information, including the gas response curve, are logged by the MX 43.

IP65 certified, the OLCT 10N is approved for use in ingress protected.

Characteristics

Attribut
Size
Valeur
4.6 x 4.3 x 2.4 in. (11.8 x 11.0 x 6.0 cm)
Attribut
Housing materials
Valeur
ABS
Attribut
Humidity
Valeur
Electrochemical sensors: 15-90 %RH, non-condensing
Catalytic sensors: 0-100 %RH, non-condensing
Attribut
Power supply
Valeur
12-30 Vcc
Attribut
Consumption
Valeur
Electrochemical sensor: 2.5 mA in normal operation @ 24 Vdc
Catalytic sensor : 50 mA in normal operation @ 24 Vdc
CO2 Infrared sensor: 20mA in normal operation @24Vdc
Attribut
Connection
Valeur
Up to 32 detectors at 1000 m with a 0.9 mm² (AWG 18) core size cable
Up to 8 explosive gas detectors at 225 m with a 0.9 mm² (AWG 18) core size cable
Attribut
Protection Class
Valeur
IP65
Attribut
Approval
Valeur
In progress :
ATEX: Ex nA nC IIC T4 Gc for explosimetric versions / Ex nA IIC T4 Gc for others (except CO2 versions)
IECEx: II 3 GD - IECEx 11.0029X
EMC: Electromagnetic compatibility according to EN50270
Attribut
Warranty
Valeur
2years

Features

  • Detection of combustible gases, toxic gases or oxygen
  • Digital technology
  • Non-intrusive calibration
  • Cost savings on wiring installation

OLCT 10N Fixed Gas Detector - User reviews

Add a review & rate this product

* required fields

Restricted HTML

  • Allowed HTML tags: <a href hreflang> <em> <strong> <cite> <blockquote cite> <code> <ul type> <ol start type> <li> <dl> <dt> <dd> <h2 id> <h3 id> <h4 id> <h5 id> <h6 id>
  • Lines and paragraphs break automatically.
  • Web page addresses and email addresses turn into links automatically.