SEARCHPOINT OPTIMA PLUS Fixed Gas Detector

SEARCHPOINT OPTIMA PLUS Fixed Gas Detector
Certification BE ATEX

WHY CHOOSE BE ATEX

  • Re-calibrate of gas detection equipments
  • Check and verify of all PPE equipements
  • Customised configuration of all devices
Entête

The infrared gas detector that provides unbeatable performance.

The Searchpoint Optima Plus is an infrared fixed-point gas sensor certified for use in potentially explosive atmospheres.

The unit’s infrared detection principle offers the fastest speed of response and fail-to-safe operation, ensuring that your staff are protected, and your production facilities can deliver maximum uptime.

Reduced routine maintenance, when compared with conventional electrocatalytic-based gas sensors, ensures a low ongoing cost of ownership. Advanced internal fault diagnostics and false alarm rejection algorithms ensure the Searchpoint Optima Plus delivers the highest level of operational integrity.

Different connection options are available :

  • Honeywell Analytics junction box
  • OELD junction box
  • XNX universal transmitter

Characteristics

Attribut
Size
Valeur
6.30 x 2.75 in. / 16.5 x 7.3 cm (optima only)
Attribut
Weight
Valeur
2.2 lbs / 1.6 kg
Attribut
Operating temperature
Valeur
-40°F to 149°F / -40°C to +65°C
Attribut
Humidity
Valeur
0 to 99% HR (non condensing)
Attribut
Humidity
Valeur
0 to 99% HR (non condensing)
Attribut
Protection Class
Valeur
IP66 / IP67
Attribut
Warranty
Valeur
3 years
Attribut
Approval
Valeur
ATEX: II 2 GD Ex d IIC Gb Ex tb IIIC Db, T96°C (Tamb -40°C to +65°C), T86°C (Tamb -40°C to +55°C)
IECEx: Ex d IIC tb IIIC T86°C (Tamb -40°C to +55°C) or T96°C (Tamb -40°C to +65°C) IP66/67
EMC: EN 50270:2006, EN 50271:2010
Performance: CSA C22.2 152., FM ANSI/ISA-12.13.01., EN 60079-29-1 (BVS 03 ATEX G 016 X), Functional Safety IEC61508 Safety Integrity Level 2
Attribut
Housing materials
Valeur
316L Stainless Steel
Attribut
Power supply
Valeur
18-32Vdc (24Vdc nom), < 4.5W max
Attribut
Consumption
Valeur
< 4,5 W max
Attribut
Connection
Valeur
3-wire shielded cable (if using 4-20mA output)

Features

  • Self-monitoring operation
  • Fast response time
  • Reduced routine maintenance
  • Immune to catalytic poisons
  • Extended service lifetime
  • Can be used in inert atmospheres
  • Dynamic heating control ensures condensation-free optics
  • Reduced power consumption
  • Over 100 gas and vapour calibrations available

SEARCHPOINT OPTIMA PLUS Fixed Gas Detector - User reviews

Add a review & rate this product

* required fields

Restricted HTML

  • Allowed HTML tags: <a href hreflang> <em> <strong> <cite> <blockquote cite> <code> <ul type> <ol start type> <li> <dl> <dt> <dd> <h2 id> <h3 id> <h4 id> <h5 id> <h6 id>
  • Lines and paragraphs break automatically.
  • Web page addresses and email addresses turn into links automatically.