QUASAR 900 Open Path Gas Detector

QUASAR 900 Open Path Gas Detector
QUASAR 900 Open Path Gas Detector
Entête

The open path detector for detection of gases over long distances.

The SafEye open path detector detects hydrocarbons by analysing atmospheric absorption and comparing it with a zone that is not affected by the presence of gas.

The open path detector consists of an infrared transmitter and an infrared receiver which can be placed up to 200 metres apart.

The SafEye detection system can replace up to 20 fixed-point gas detectors. It will help you optimise your investment and maintenance costs. There are just two detectors to install, keeping maintenance costs to a minimum, and just one consumable with a long service lifetime to be replaced periodically.

Characteristics

Attribut
Size
Valeur
Detector/source: 10.5 x 5.1 x 5.1 in. (26.7 x 13.0 x 13.0 cm)
Tilt mount: 4.7 x 4.7 x 5.5 in. (12.0 x 12.0 x 15.8 mm)
Attribut
Weight
Valeur
Detector/source: 11 lb. (5 kg)
Tilt mount: 4.2 lb. (1.9 kg)
Attribut
Operating temperature
Valeur
-67 to +149 °F (-55 to +65 °C)
Attribut
Humidity
Valeur
0-95 %RH (non condensing)
Attribut
Housing materials
Valeur
Stainless steel
Attribut
Power supply
Valeur
24 Vdc nominal (18-32 Vdc)
Attribut
Consumption
Valeur
Detector: 250 mA (300 mA peak)
Source: 250 mA (300 mA peak"
Attribut
Protection Class
Valeur
IP66 and IP68, NEMA 250 6P
Attribut
Approval
Valeur
ATEX and IECEx:
Ex II 2 (2)G D, Ex db eb ib [ib Gb] IIB + H2 T4 Gb
Ex tb IIIC T135 °C Db Ta = -55 °C to +65 °C
SIL2 per IEC61508 (TUV)
Attribut
Warranty
Valeur
3 years

Features

  • Multi-combustible gas detection
  • Range of 200 meters
  • Fast response (< 3 seconds) gives quick alert to hazards
  • Connects easily to existing systems
  • Heated optics provide unfettered Detection in most environments
  • Intrinsically Safe communication port can be used with HART® Hand-Held in non-safe areas for setup and diagnostics
  • RS-485, Modbus
Quasar 900
miniature

QUASAR 900 Open Path Gas Detector - User reviews

Add a review & rate this product

* required fields

Restricted HTML

  • Allowed HTML tags: <a href hreflang> <em> <strong> <cite> <blockquote cite> <code> <ul type> <ol start type> <li> <dl> <dt> <dd> <h2 id> <h3 id> <h4 id> <h5 id> <h6 id>
  • Lines and paragraphs break automatically.
  • Web page addresses and email addresses turn into links automatically.